InteliLite Global Guide
537
LBI: S
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
44
Description
If this input is active, all alarms except Emergency Stop and Overspeed are suppressed. The suppressed
alarms will be displayed in the alarm list, but they will not take effect regarding the gen-set control.
Note:
is indicated in the alarm list if Sd Override mode is active to inform the
operator that the engine is not protected.
IMPORTANT: MISUSE OF THIS INPUT CAN CAUSE DAMAGE TO THE GEN-SET!
Sd Override
back to Logical binary inputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
189
Description
Binary input has the same function as Start Button
on the InteliLite front panel. It is evaluated in MAN
mode only.
Start Button
back to Logical binary inputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
190
Description
Binary input has the same function as Stop Button
on the InteliLite front panel. It is evaluated in MAN
Mode only.
Stop Button
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...