InteliLite Global Guide
51
5 Controller setup
5.2 Controller configuration and PC tools connection
5.1 Default configuration
5.1.1 Binary inputs
Number
Description
Configured function
BIN1
Remote start/stop command
BIN2
Access lock keyswitch
BIN3
Emergency stop button
BIN4
Switch controller to OFF mode
BIN5
Suppression of alarms
BIN6
Control lock keyswitch
BIN7
Free slot
5.1.2 Binary outputs
Number
Description
Function
BOUT1
Starter motor control
BOUT2
Fuel solenoid valve
BOUT3
Indication of breaker state
BOUT4
Activation of any devices before start
BOUT5
Gen-set can be connected to load
BOUT6
Indication of unconfirmed alarm
BOUT7
Free slot
5.1.3 Analog inputs
Number
Configured sensor
Function
AIN1
VDO 10 Bar
AIN2
VDO40-120°C
AIN3
VDOLevel %
AIN4
None