InteliLite Global Guide
162
Password
This password is the same as in InteliConfig or directly in controller.
Table
Register addresses
Number of registers
Access
Data type
Meaning
4211
1
write
Unsigned16
Password
Note:
Default password is "0".
In this example the password is "1234".
Request: (Numbers in Hex)
01
06
10
73
04
D2
7C
D1
Controller address
Modbus function
Register address
1073
hex
=
4211
dec
Password
04D2
hex
=
1234
dec
CRC
Response for success: (Numbers in Hex)
01
06
10
73
00
00
7C
D1
Controller address
Modbus function
Register address
1073
hex
=
4211
dec
Allways zero.
CRC
Response for bad password: (Numbers in Hex)
01
86
04
43
A3
Controller
address
Modbus exception
for function 6.
04 – device error
see Error codes (exception codes) on page 155
CRC
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...