InteliLite Global Guide
106
IMPORTANT: It is necessary to configure breaker feedback to use this function.
IMPORTANT: Also it is possible to use breakers without feedbacks. In this case there is no check
of breaker real state.
There are three different time delays for breaker fail detection – see following diagrams.
When binary output breaker close/open is in steady state and breaker feedback is changed the breaker fail is
detected immediately (no delay).
Image 5.19 Breaker fail - breaker close/open in steady position - open
Image 5.20 Breaker fail - breaker close/open in steady position - close
When binary output breaker close/open opens there is 2 sec delay for breaker fail detection.