InteliLite Global Guide
198
Subgroup: Starting Timers
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0,0 .. 25,0 [s]
Default value
0,5 s
Alternative config
NO
Step
0,1 s
Comm object
10525
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Delay between
and
logical binary outputs.
is closed before
. Lead time is adjusted via this setpoint.
Image 8.2 Fuel Solenoid Lead
Note:
LBO
goes to logical zero when Fuel Solenoid Lead goes to logical one.
Note:
This setpoint is used only for diesel
Fuel Solenoid Lead
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 600 [s]
Default value
12 s
Alternative config
NO
Step
1 s
Comm object
9097
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Idle Time delay starts when RPM exceeds
. Start fail is detected when during Idle
state RPM decreases below 2 RPM.
The output
remains inactive during the idle period. Binary output Idle/Nominal
opens during Cooling period again. This output can be used for switching the governor between idle and
Idle Time
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...