InteliLite Global Guide
227
Group: Generator settings
Subgroup: Overload Protection
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
.. 200 [%]
Default value
120 %
Alternative config
NO
Step
1 % of
Comm object
8280
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold level for generator overload (in % of Nominal power) protection. Protection is BOC (Breaker Open
and gen-set Cooldown).
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Overload BOC
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
0 ..
[%]
Default value
120 %
Alternative config
NO
Step
1 % of
Comm object
9685
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold level for generator overload (in % of Nominal power) protection. This is only warning.
Overload Wrn
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
0,0 .. 600,0 [s]
Default value
5,0 s
Alternative config
NO
Step
0,1 s
Comm object
8281
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
Overload BOC (page 227)Overload BOC (page 227)
and
protection.
Overload Delay
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...