InteliLite Global Guide
161
Starting the engine
Before starting engine you may need to write password. Depends on your settings in controller.
Table
Register addresses
Number of registers
Access
Data type
Meaning
4207 - 4208
2
read/write
Unsigned32
Writing:command argument
Reading: command return value
4209
1
write
Unsigned16
Command code
Table
List of commands and arguments (page 157)
Action
Command code
Argument
Return value
Engine start
0x01
0x01FE0000
0x000001FF
Engine stop
0x01
0x02FD0000
0x000002FE
Request 1/2: (Numbers in Hex)
01
10
10
6F
00
03
06
Controller address
Modbus function
10
hex
= 16
dec
Register address
106F
hex
=
4207
dec
Number of registers
Data length in bytes
Request 2/2: (Numbers in Hex)
01
FE
00
00
00
01
68
0B
Argument
Command code
CRC
Note:
Command and argument may be written as one "packet" (function 16) or you can split it and write
argument (function 16) and after that write command code (function 6).
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...