InteliLite Global Guide
184
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
Disabled / Enabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
9983
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
If this function is enabled, the controller will switch automatically to MAN mode when there is a red alarm in
the alarm list and fault reset button is pressed. This is a safety function that prevents the gen-set starting
again automatically in specific cases when fault reset button is pressed.
Example:
Controller is in AUTO mode and there is red inactive unconfirmed alarm and fault reset
button is pressed, controller will start automatically.
Reset To Manual
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
Disabled / 1 .. 255 [min]
Default value
Disabled
Alternative config
NO
Step
1 min
Comm object
10121
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
The display backlight is switched off when this timer exceed. When setpoint is adjusted to disabled then the
display will be backlighted all the time.
Backlight Timeout
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...