InteliLite Global Guide
183
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
AMF / MRS [-]
Default value
AMF
Alternative config
NO
Step
[-]
Comm object
12157
Related applications
AMF
Config level
Advanced
Setpoint visibility
Always
Description
Based on this setpoint is defined basic controller function.
AMF
Normal AMF operation
MRS
When MRS mode is selected the controller will not perform AMF functions anymore. MCB
button
will be inactive and also mains measurement and protections will be disabled.
The controller will keep TEST mode and the gen-set in AUTO mode will be able to start by
binary input.
Operation Mode
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
1 .. 32 [-]
Default value
1
Alternative config
NO
Step
1
Comm object
24537
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Controller identification number. It is possible to set controller address different from the default value (1) so
that more IL controllers can be interconnected (via RS485) and accessed e.g. from MODBUS terminal.
Note:
When opening connection to the controller it's address has to correspond with the setting in PC
tool.
Note:
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Controller Address
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...