InteliLite Global Guide
711
9. Wait till process is done (If the process doesn’t start – after 60 second the “Timeout” will be evaluated. In this
case please check:
You have proper connection with the unit
COM port selection is correct
Module has power supply, (no CAN bus connection, status LED lights continuously)
10. After successful programming disconnect AT-Link conv , remove TEST jumper and disconnect power
supply
11. Connect power supply again (status LED should blinking)
12. Module FW is upgraded
LED indication
LED status
Description
Dark
Fw in module does not work correctly.
Flashing
Module does not communicate with controller (in case non-zero CAN address).
Lights
Power supply is in the range and the communication between Inteli AIN8 and controller
works properly.
Or power supply is in range and zero CAN address is set. (in case zero CAN address
module doesn’t communicate with the controller).
Wiring
The following diagrams show the correct connection of sensors.
Terminator
Resistance sensor - 3 wires
Note:
Ranges: Pt100, Pt1000, Ni100, Ni1000, 0 – 2400 Ω, 0 – 10 kΩ
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...