InteliLite Global Guide
200
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
1 ..
Maximal Stabilization Time (page 201)
[s]
Default value
2 s
Alternative config
NO
Step
1 s
Comm object
8259
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
When the gen-set has been started and the idle timer has elapsed, the controller will wait for a period
adjusted by this setpoint before closing GCB, even if the generator voltage and frequency are already in
limits.
Image 8.5 Minimal Stabilization Time
Minimal Stabilization Time