InteliLite Global Guide
132
Control of After-Treatment regeneration function
User can force or inhibit regeneration process by activating appropriate binary inputs of the controller. Please
see the list of binary inputs below:
5.5.23 Alternate configuration
In controller are 3 sets of configuration.
Configuration set 1
Configuration set 2
Configuration set 3
Nominal Frequency 1 (page 331)
Nominal Frequency 2 (page 335)
Nominal Frequency 3 (page 339)
Configuration sets can be changed via logical binary inputs
and
. Configuration set 1 is active when there is no input activated. In case that inputs
and
are active at the same time, the
configuration set 3 is took in account.
Active configuration set
0
0
1
1
0
2
0
1
3
1
1
3
IMPORTANT: If LBO
is used, change of alternate configuration can
be made only in prestart phase. So prestart has to be set up for enough long time.