InteliLite Global Guide
341
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
1 .. 5 000 [kW]
Default value
200 kW
Alternative config
Yes
Step
1 kW
Comm object
12048
Related applications
AMF, MRS,
Config level
Standard
Setpoint visibility
Always
Description
Nominal power of the gen-set. Generator
protection is based on this setpoint.
Note:
This setpoint is used when setpoint
is adjusted to Monophase or
Splitphase or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect detects connection type as
3Ph3Wire or High Leg D or 3Ph4Wire.
Note:
This value is used when binary input
is active.
Nominal Power 3
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
1 .. 5 000 [kW]
Default value
200 kW
Alternative config
Yes
Step
1 kW
Comm object
15773
Related applications
AMF, MRS,
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal power of the gen-set for detected split-phase or mono phase connection. Generator
protection is based on this setpoint.
Note:
This setpoint is used when setpoint
is adjusted to Autodetect and
Autodetect detects connection type as Monophase or Splitphase.
Note:
This value is used when binary input
is active.
Nominal Power Split Phase 3
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...