InteliLite Global Guide
177
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
1 .. 5 000 [A/5A]
Default value
2 000 A/5A
Alternative config
NO
Step
1 A/5A
Comm object
8274
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Gen-set current transformers ratio.
Note:
Generator currents and power measurement is suppressed if current level is below 1% of CT
range.
CT Ratio
Subgroup: Voltage settings
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
Mono Phase / SplPhL1L2 / SplPhL1L3 / 3Ph3Wire / 3Ph4Wire / High Leg D /
Autodetect [-]
Default value
3Ph4Wire
Alternative config
YES
Step
[-]
Comm object
11628
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Connection type:
Mono Phase
Single phase voltage measurement L1-N
1x CT (Current Transformer)
SplitPhase
Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
SplPhL1L2
Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
SplPhL1L3
Double Delta connection
Split Phase
Two phase voltage measurement L1,L3 with 180° phase shift
Connection type
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...