InteliLite Global Guide
545
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
3
Description
Output closes when any warning alarm appears.
The output opens, if:
No warning alarm is active and
Fault reset
button is pressed
AL Common Wrn
back to Logical binary outputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
1295
Description
The output is closed when there is the
Wrn Coolant Temperature Low (page 656)
alarm from the
in the alarmlist or isn’t confirmed.
AL CoolantTemp Low
Logical binary outputs alphabetically (page 539)
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
1421
Description
The output is closed when there is the shutdown or BOC alarm from the
in the
alarmlist or isn’t confirmed.
AL CoolantTemp Sd
Logical binary outputs alphabetically (page 539)
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
1420
Description
The output is closed when there is the warning alarm from the
in the alarmlist or
isn’t confirmed.
Note:
Binary output is also active if protection type is set to HistRecOnl and threshold level for history
record is reach.
AL CoolantTemp Wrn
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...