InteliLite Global Guide
201
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
Minimal Stabilization Time (page 200)
.. 300 [s]
Default value
10 s
Alternative config
NO
Step
1 s
Comm object
8313
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
When the gen-set has been started and the idle timer has elapsed, the generator voltage and frequency must
get within limits within this period of time, otherwise an appropriate shutdown alarm (generator voltage and/or
frequency) is issued.
Image 8.6 Maximal Stabilization Time
Maximal Stabilization Time
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0,0 .. 300,0 [s]
Default value
5,0 s
Alternative config
YES
Step
0,1 s
Comm object
10023
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
During the start of the gen-set, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the Protect Hold Off. The time starts after reaching Starting RPM.
Protection Hold Off
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...