InteliLite Global Guide
687
Related applications
AMF, MRS
Description
This alarm evaluates the unbalance of the phase to phase voltages, i.e. the
difference between highest and lowest phase to phase voltage at any given time.
The following setpoints are related to it:
Voltage Unbalance BOC (page 232)
adjusts the maximum allowed
difference between the highest and lowest phase voltage at any given time.
Voltage Unbalance BOC Delay (page 233)
adjusts the alarm delay.
back to List of alarms level 2
Alarm Type
BOC
Alarmlist message
BOC Gen Voltage Unbalance ph-n
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the unbalance of the phase voltages, i.e. the difference
between highest and lowest phase voltage at any given time. The following
setpoints are related to it:
Voltage Unbalance BOC (page 232)
adjusts the maximum allowed
difference between the highest and lowest phase voltage at any given time.
Voltage Unbalance BOC Delay (page 233)
adjusts the alarm delay.
BOC Gen Voltage Unbalance Ph-N
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd + Name of binary input
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
The overcurrent alarm is based on IDMT principle. The reaction time of an IDMT
alarm is not fixed, but depends on how much is the protected value (generator
current in this case) above the limit (
). The higher is
the overcurrent, the shorter the reaction time will be. All generator phases are
evaluated.
The behaviour of the overcurrent alarm is adjusted by the following setpoints:
IDMT Overcurrent Delay (page 229)
defines the reaction time of the
protection when the current is twice the amount of nominal value.
set the nominal current level, where the
alarm starts to be evaluated. The reaction time is infinite at this point.
BOC Overcurrent IDMT
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...