InteliLite Global Guide
733
Analog outputs
1 channel AOUT1. Type of output:
0-10V DC
0-20mA
PWM (5V, freq 2,4Hz ÷2,4kHz)
Analog output has 4-pins connector – GND and one pin for each type of output.
All analog inputs can be configured to any logical function or protection.
Supported sensors
Sensors
User curves
PT1000 [°C] (fix)
NI1000 [°C] (fix)
0-2400Ω (fix linear)
± 65 V DC (fix linear)
+-75mV (fix linear)
Thermocpl J [°C] (fix)
Thermocpl K [°C] (fix)
Thermocpl L [°C] (fix)
Thermocpl (nc) J [°C] (fix)
Thermocpl (nc) K [°C] (fix)
Thermocpl (nc) L [°C] (fix)
Thermocpl (nc) J [°F] (fix)
Thermocpl (nc) K [°F] (fix)
Thermocpl (nc) L [°F] (fix)
Address and DIP switch setting
Address configuration
DIP switch determinates CAN address for analog inputs and outputs.
Programming Firmware
Firmware upgrade is via AT-link (TTL). For programming it is necessary to close jumper TEST and switch OFF
and switch ON the power supply.
For programming use FlashProg PC tool version 4.4 or higher.
LED indication
LED status
Description
Dark
Fw in module does not work correctly.
Flashing
Module does not communicate with controller (in case non-zero CAN address)
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...