InteliLite Global Guide
41
Analog inputs are typically used for: Oil Pressure, Coolant Temperature and Fuel Level. All of these parameters
are connected with relevant protections.
Image 4.19 Grounded sensors
Image 4.20 Isolated sensors
Note:
Schemes show only analog input connection overview, not actual wiring.
Note:
The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.
Analog inputs with voltage & current sensors
On each analog input, there is a possibility to connect voltage or current output sensor instead of resistive one.
Recommended wiring connection for these measurements and recommended curves are bellow.
Voltage sensors
Sensor’s output
range (V)
R1 (Ω)
R2 (Ω)
0 - 10
390
100
0 - 30
1500
100
0 - 70
3300
100