InteliLite Global Guide
207
Subgroup: Engine Protections
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
.. 200 [%]
Default value
115%
Alternative config
NO
Step
1 % of
Comm object
8263
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for over speed protection. Relative to the nominal speed.
Overspeed Sd
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 ..
[%]
Default value
25%
Alternative config
NO
Step
1 % of
Comm object
8260
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for underspeed protection. Relative to the nominal speed.
Underspeed Sd
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 50 [%]
Default value
20%
Alternative config
NO
Step
1 % of
Comm object
14107
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
This setpoint rise the upper limit of overspeed protection for the time which is defined in setpoint
. In this time the upper limit of protection is
+
Overspeed Overshoot.
Overspeed Overshot
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...