InteliLite Global Guide
189
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
Diesel / Gas [-]
Default value
Diesel
Alternative config
NO
Step
[-]
Comm object
9100
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Determines behavior of the Binary output
Diesel:
Output closes before binary output
. Lead of output is adjusted via
setpoint
. The output opens if Emergency Stop comes
or gen-set is stopped and in pause between repeated starts.
Gas:
(Gaseous)
Output closes together with binary output
if RPM is over the 30
RPM (fixed value). Output opens after stop command or in pause between repeated
start.
Fuel Solenoid
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
1 .. 10 [-]
Default value
3
Alternative config
NO
Step
1
Comm object
8255
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maximal number of cranking attempts.
Cranking Attempts
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...