InteliLite Global Guide
597
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
24
Description
This output is dedicated for starter motor control. The number of cranking attempts is adjusted by setpoint
in Engine Settings group. Cranking fail pause is adjusted by setpoint
Cranking Fail Pause (page 190)
.
Image 8.185 Starter
The starter output opens when:
the “firing” speed is reached
maximum time of cranking is exceeded
request to stop comes up
D+ value is higher than
Oil pressure value is higher than
Starting Oil Pressure (page 192)
Generator voltage > 25% of
Nominal Voltage Ph-N (page 179)
or
(any phase)
Starter
back to Logical binary outputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
26
Description
Logical binary output which is still in logical 0.
Still Log 0
back to Logical binary outputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
27
Description
Logical binary output which is still in logical 1.
Still Log 1
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...