InteliLite Global Guide
190
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
1 .. 255 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
8256
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Maximum time limit of cranking time.
IMPORTANT: There is a protection against broken pinion on starter. In case that there are no
RPM after 5 seconds of starting, cranking is interrupted and cranking fail pause follows.
Maximum Cranking Time
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
5 .. 60 [s]
Default value
8 s
Alternative config
NO
Step
1 s
Comm object
8257
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Pause between
output is active in this pause until
Cranking Fail Pause elapses.
Cranking Fail Pause
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...