InteliLite Global Guide
202
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 60 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
9695
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
In case
is set to GAS, the Sd Ventilation Time adjusts the time of the starter to
be switched on for engine pre-ventilation in the case of a first start attempt after shutdown or controller
switch-on.
Sd Ventilation Time
Subgroup: Stopping
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
Idle / Nominal [-]
Default value
Nominal
Alternative config
NO
Step
[-]
Comm object
10046
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Selects the function of the binary output
during engine cooling state.
Idle
Cooling is executed at Idle speed and generator protections are switched off.
Nominal
Cooling is executed at Nominal speed and generator protections are active.
Note:
When ECU is connected the predefined value 900 RPM for Idle speed is requested.
Note:
Binary output
must be configured and connected to speed governor.
Engine Idle speed must be adjusted on speed governor.
Cooling Speed
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...