InteliLite Global Guide
632
LAI: F
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
78
Description
Logical analog input designed for fuel level value received from analog sensor. For more information about wiring
of analog inputs
. Limits for this protection are adjusted by setpoints
and
. Delay is adjusted by setpoint
Monitoring
Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl
Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
Wrn
Analog value is used for warning protection only.
Wrn + BOC
Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC
Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd
Analog value is used for warning and shutdown protection.
Sd
Analog value is used for shutdown protection.
Protection types
Note:
This parameter has to be adjusted via InteliConfig.
Under limit
Alarm is activated when value of analog input is under adjusted limits
Over limit
Alarm is activated when value of analog input is over adjusted limits
Under limit + fls
Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls
Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Alarm
Example:
Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be act
Sensor fail alarm will be activated.
Note:
This parameter has to be adjusted via InteliConfig.
IMPORTANT: For right behavior of this function, curve for analog input has to be in
percentage and setpoint
has to be adjusted correctly.
Note:
This analog function can by also configured on binary input as binary function. In this case chose
binary input in the list of binary inputs. Delay of this binary input is adjusted via
the same setpoint like for analog function.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Fuel Level
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...