InteliLite Global Guide
214
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 900 [s]
Default value
5 s
Alternative config
YES
Step
1 s
Comm object
10270
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if the logical analog input
is configured
Description
Delay for
Coolant Temperature Low Wrn (page 213)
.
Coolant Temperature Low Delay
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config
NO
Step
the step is defined by analog sensor curve
Comm object
12897
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible only if the logical analog input
is configured
Description
Warning or history threshold level for
Fuel Level Wrn
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config
NO
Step
the step is defined by analog sensor curve
Comm object
12898
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible only if the logical analog input
is configured
Description
Shutdown or BOC threshold level for
Fuel Level Sd
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...