InteliLite Global Guide
179
or
L3 >=100V
Mono Phase
or
L1 >=100V
L2 <= 20V
L3 <= 20V
Voltage Autodetect
shutdown
Note:
To lock this setpoint against editing you also have to lock setpoint
and
.
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
80 .. 20 000 [V]
Default value
231 V
Alternative config
YES
Step
1 V
Comm object
8277
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
.
Description
Nominal voltage (phase to neutral).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Voltage Ph-N 2 (page 336)
and
Nominal Voltage Ph-N 3 (page 340)
.
Nominal Voltage Ph-N
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
80 .. 40 000 [V]
Default value
400 V
Alternative config
YES
Step
1 V
Comm object
11657
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
.
Description
Nominal system voltage (phase to phase).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Voltage Ph-Ph 2 (page 336)
and
Nominal Voltage Ph-Ph 3 (page 340)
Nominal Voltage Ph-Ph
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...