InteliLite Global Guide
216
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 900 [s]
Default value
10 s
Alternative config
NO
Step
1 s
Comm object
14433
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible only if ECU is configuredd
Description
Delay for Fuel level which is send from ECU.
ECU Fuel Level Delay
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 10 000 [l]
Default value
200 l
Alternative config
YES
Step
1 l
Comm object
11103
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if the logical analog input
is or ECU is configured
Description
Define a capacity of gen-set fuel tank.
Fuel Tank Volume
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
Disabled / 1 .. 50 [%/h]
Default value
25 %/h
Alternative config
NO
Step
1%/h
Comm object
12373
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Setpoint indicates the maximum allowable drop of fuel in fuel tank per running hour. When the engine is not
running the maximal allowed fuel drop-off is preset to 5% of total tank volume per hour.
Maximal Fuel Drop
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...