InteliLite Global Guide
176
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
1 .. 5 000 [kW]
Default value
200 kW
Alternative config
Yes
Step
1 kW
Comm object
8276
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Nominal power of the gen-set. Generator
protection is based on this setpoint.
Note:
This setpoint is used when setpoint
is adjusted to 3Ph3Wire or High
Leg D or 3Ph4Wire or when Autodetect detects connection type as 3Ph3Wire or High Leg D or
3Ph4Wire.
Note:
To lock this setpoint against editing you also have to lock setpoint
,
and
Nominal Power
Subgroup: Current settings
Setpoint group
Basic settings
Related FW
1.9.0
Range [units]
1 .. 10 000 [A]
Default value
350 A
Alternative config
YES
Step
1 A
Comm object
8275
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
.
Description
It is current limit for mains current protections and means maximal continuous mains current. Nominal
Current can be different from mains rated current value.
Note:
To lock this setpoint against editing you also have to lock setpoint
and
Nominal Current
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...