InteliLite Global Guide
587
When the
is shorter than
Cranking Fail Pause (page 190)
then the
in
Cranking Fail Pause (page 190)
is long as normal
Image 8.183 Prestart in Cranking Fail Pause 2
back to Logical binary outputs alphabetically
LBO: R
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
58
Description
The output is closed whenever the GCB is closed or can be closed i.e. the stabilization phase is finished, the
gen-set is running and the
Minimal Stabilization Time (page 200)
timer has elapsed.
and the gen-set voltage and frequency are within limits.
If GCB is open then gen-set voltage and frequency must be in limits.
If GCB is close then gen-set voltage and frequency can be out of limits, but protection delay can’t be count
down. If gen-set voltage and frequency will return into limits until delay is count down then output is still
closed.
Ready To Load
back to Logical binary outputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
62
Description
The binary output is closed, when the engine is stopped and it is possible to start it i.e. no red alarm is
activated or
is active.
The binary output is switch on when the Ready state occurs.
The binary output is switch off when the Prestart or the Not Ready or the Stop state occurs i.e. always
except Ready state.
Ready
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...