0.8
load
RFPEZx
Z
EQUATION792 V2 EN-US
(Equation 218)
This equation is applicable only when the loop characteristic angle for the single
phase-to-earth faults is more than three times as large as the maximum expected
load-impedance angle. More accurate calculations are necessary according to the
equation below:
min
2
1
0
0.8
cos
sin
2
1
0
load
R Zx
R Zx
RFPEZx
Z
X Zx
X Zx
EQUATION578 V5 EN-US
(Equation 219)
Where:
ϑ
is a maximum load-impedance angle, related to the minimum load impedance conditions.
All this is applicable for all measuring zones when no power swing detection
element is in the protection scheme. Use an additional safety margin of
approximately 20% in cases when a power swing detection element is in the
protection scheme, refer to the description of the power swing detection
(ZMRPSB) function.
8.5.3.8
Load impedance limitation, with load encroachment function
activated
SEMOD154704-129 v1
The parameters for load encroachment shaping of the characteristic are found in the
description of the phase selection with load encroachment function, section
"Resistive reach with load encroachment characteristic"
. If the characteristic for the
impedance measurement shall be shaped with the load encroachment algorithm, the
parameter
OperationLdCmp
in the phase selection has to be switched
On
.
8.5.3.9
Setting of minimum operating currents
SEMOD154704-132 v2
The operation of the distance function will be blocked if the magnitude of the
currents is below the set value of the parameter
IMinOpPE
.
The default setting of
IMinOpPE
is 20% of
IBase
where
IBase
is the chosen base
current for the analog input channels. The value have been proven in practice to be
suitable in most of the applications. However, there might be applications where it
is necessary to increase the sensitivity by reducing the minimum operating current
down to 10% of the IED base current. This happens especially in cases, when the
IED serves as a remote back-up protection on series of very long transmission
lines.
If the load current compensation is activated, there is an additional criteria
IMinOpIN
that will block the phase-earth loop if the 3I0<
IMinOpIN
. The default
setting of
IMinOpIN
is 5% of the IED base current
IBase
.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
281
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...