The setting of
DU>
should be set high (approximately 60% of
UBase
) and the
current threshold
DI<
low (approximately 10% of
IBase
) to avoid unwanted
operation due to normal switching conditions in the network. The delta current and
delta voltage function shall always be used together with either the negative or zero
sequence algorithm. If
USet
prim
is the primary voltage for operation of dU/dt and
ISet
prim
the primary current for operation of dI/dt, the setting of
DU>
and
DI<
will
be given according to equation
.
DU
USet
UBase
prim
> =
100
.
EQUATION1523 V3 EN-US
(Equation 531)
DI
ISet
IBase
prim
< =
100
.
EQUATION1524 V4 EN-US
(Equation 532)
The voltage thresholds
UPh>
is used to identify low voltage condition in the
system. Set
UPh>
below the minimum operating voltage that might occur during
emergency conditions. A setting of approximately 70% of
UBase
is recommended.
The current threshold
IPh>
shall be set lower than the
IMinOp
for the distance
protection function. A 5...10% lower value is recommended.
14.2.3.6
Dead line detection
M13683-78 v4
The condition for operation of the dead line detection is set by the parameters
IDLD<
for the current threshold and
UDLD<
for the voltage threshold.
Set the
IDLD<
with a sufficient margin below the minimum expected load current.
A safety margin of at least 15-20% is recommended. The operate value must
however exceed the maximum charging current of an overhead line, when only one
phase is disconnected (mutual coupling to the other phases).
Set the
UDLD<
with a sufficient margin below the minimum expected operating
voltage. A safety margin of at least 15% is recommended.
14.3
Fuse failure supervision VDSPVC
GUID-9C5BA1A7-DF2F-49D4-A13A-C6B483DDFCDC v2
14.3.1
Identification
GUID-109434B0-23E5-4053-9E6E-418530A07F9C v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision
VDSPVC
VTS
60
Section 14
1MRK 506 369-UEN B
Secondary system supervision
592
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...