SETON
Indicates that auto recloser is switched on and operative.
SUCCL
If the circuit breaker closing command is given and the circuit breaker is closed
within the set time interval
tUnsucCl
, the
SUCCL
output is activated after the set
time interval
tSuccessful
.
SYNCFAIL
The
SYNCFAIL
output indicates that the auto recloser is inhibited because the
synchrocheck or energizing check condition has not been fulfilled within the set
time interval, tSync. Also
ABORTED
output will be activated.
UNSUCCL
Indicates unsuccessful reclosing.
WFMASTER
Wait from master is used in high priority units to hold back auto reclosing of the
low priority unit during sequential auto reclosing. Refer to the recommendation for
multi-breaker arrangements in Figure
.
Connection and setting examples
is showing an example of how to connect the auto recloser when used
for three-phase auto reclosing and Figure
is showing an example of how to
connect the auto recloser when used for single-phase, two-phase or three-phase
auto reclosing.
Section 15
1MRK 506 369-UEN B
Control
630
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...