CutPulse
: In circuit breakers without anti-pumping relays, the setting
CutPulse
=
On
can be used to avoid repeated closing operation when reclosing onto a fault. A
new start will then cut the ongoing pulse.
tPulse
: The circuit breaker closing command should be long enough to ensure
reliable operation of the circuit breaker. The circuit breaker closing command pulse
has a duration set by the
tPulse
setting. A typical setting may be
tPulse
= 200 ms.
A longer pulse setting may facilitate dynamic indication at testing, for example, in
debug mode of the Application Configuration Tool (ACT) in PCM600. In circuit
breakers without anti-pumping relays, the setting
CutPulse
=
On
can be used to
avoid repeated closing operations when reclosing onto a fault. A new start will then
cut the ongoing pulse.
tReclaim
: The reclaim time sets the time for resetting the function to its original
state, after which a line fault and tripping will be treated as an independent new
case with a new auto reclosing cycle. One may consider a nominal CB duty cycle
of for instance, O – 0.3sec – CO – 3min – CO. However the 3 minute (180 s)
recovery time is usually not critical as fault levels are mostly lower than rated value
and the risk of a new fault within a short time is negligible. A typical time may be
tReclaim
= 60 or 180 s dependent on the fault level and circuit breaker duty cycle.
tSync
: Maximum wait time for fulfilled synchrocheck conditions. The time window
should be coordinated with the operate time and other settings of the synchrocheck
function. Attention should also be paid to the possibility of a power swing when
reclosing after a line fault. Too short a time may prevent a potentially successful
auto reclosing.
tCBClosedMin
: A typical setting is 5.0 s. If the circuit breaker has not been closed
for at least this minimum time, an auto reclosing start will not be accepted.
tSuccessful
: If the circuit breaker closing command is given and the circuit breaker
is closed within the set time interval
tUnsucCl
, the
SUCCL
output is activated after
the set time interval
tSuccessful
.
tUnsucCl
: The reclaim timer,
tReclaim
, is started each time a circuit breaker
closing command is given. If no start occurs within this time, the auto recloser will
reset. A new start received in “reclaim time” status will reenter the auto recloser to
“in progress” status as long as the final shot is not reached. The auto recloser will
reset and enter “inactive” status if a new start is given during the final reclaim time.
This will also happen if the circuit breaker has not closed within set time interval
tUnsucCl
at the end of the reclaim time. This latter case is controlled by setting
UnsucClByCBChk
. The auto reclosing sequence is considered unsuccessful for
both above cases and the
UNSUCCL
output is activated.
DeadTime settings
NoOfShots
: In power transmission one shot is mostly used. In most cases one auto
reclosing shot is sufficient as the majority of arcing faults will cease after the first
auto reclosing shot. In power systems with many other types of faults caused by
1MRK 506 369-UEN B
Section 15
Control
Line distance protection REL670 2.2 IEC
637
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...