IR
IED pickup current (U>Trip/SeriesResistor)
Ires
is the current through the voltage limiter and
ΣImag
is the sum of the magnetizing currents from all CTs in the circuit (for example, 4 for
restricted earth fault protection, 2 for reactor differential protection, 3-5 for autotransformer
differential protection).
It should be remembered that the vectorial sum of the currents must be used (IEDs,
Metrosil and resistor currents are resistive). The current measurement is insensitive
to DC component in fault current to allow the use of only the AC components of
the fault current in the above calculations.
The voltage dependent resistor (Metrosil) characteristic is shown in Figure
.
Series resistor thermal capacity
SEMOD54734-336 v6
The series resistor is dimensioned for 200 W. Preferable the
U>Trip
2
/
SeriesResistor
should always be lower than 200 W to allow continuous activation
during testing. If this value is exceeded, testing should be done with a transient
faults.
Section 7
1MRK 506 369-UEN B
Differential protection
134
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...