![ABB REL670 2.2 IEC Applications Manual Download Page 578](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789578.webp)
An example will be given, how sensitive-earth-fault protection for power lines can
be achieved by using negative-sequence directional overcurrent protection
elements within a CVGAPC function.
This functionality can be achieved by using one CVGAPC function. The following
shall be done to ensure proper operation of the function:
1. Connect three-phase power line currents and three-phase power line voltages
to one CVGAPC instance (for example, GF04)
2. Set
CurrentInput
to
NegSeq
(please note that CVGAPC function measures I2
current and NOT 3I2 current; this is essential for proper OC pickup level
setting)
3. Set
VoltageInput
to
-NegSeq
(please note that the negative sequence voltage
phasor is intentionally inverted in order to simplify directionality
4. Set base current
IBase
value equal to the rated primary current of power line
CTs
5. Set base voltage
UBase
value equal to the rated power line phase-to-phase
voltage in kV
6. Set
RCADir
to value +65 degrees (
NegSeq
current typically lags the inverted
NegSeq
voltage for this angle during the fault)
7. Set
ROADir
to value 90 degree
8. Set
LowVolt_VM
to value 2% (
NegSeq
voltage level above which the
directional element will be enabled)
9. Enable one overcurrent stage (for example, OC1)
10. By parameter
CurveType_OC1
select appropriate TOC/IDMT or definite time
delayed curve in accordance with your network protection philosophy
11. Set
StartCurr_OC1
to value between 3-10% (typical values)
12. Set
tDef_OC1
or parameter “k” when TOC/IDMT curves are used to insure
proper time coordination with other earth-fault protections installed in the
vicinity of this power line
13. Set
DirMode_OC1
to
Forward
14. Set
DirPrinc_OC1
to
IcosPhi&U
15. Set
ActLowVolt1_VM
to
Block
•
In order to insure proper restraining of this element for CT saturations
during three-phase faults it is possible to use current restraint feature and
enable this element to operate only when
NegSeq
current is bigger than a
certain percentage (10% is typical value) of measured
PosSeq
current in
the power line. To do this the following settings within the same function
shall be done:
16. Set
EnRestrainCurr
to
On
17. Set
RestrCurrInput
to
PosSeq
18. Set
RestrCurrCoeff
to value 0.10
If required, this CVGAPC function can be used in directional comparison
protection scheme for the power line protection if communication channels to the
remote end of this power line are available. In that case typically two
NegSeq
overcurrent steps are required. One for forward and one for reverse direction. As
Section 12
1MRK 506 369-UEN B
Multipurpose protection
572
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...