![ABB REL670 2.2 IEC Applications Manual Download Page 320](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789320.webp)
R
X
RLdFw
RLdRv
ARGLd
ARGLd
ARGLd
ARGLd
en05000196.vsd
IEC05000196 V1 EN-US
Figure 158:
Characteristic of load encroachment function
The influence of load encroachment function on the operation characteristic is
dependent on the chosen operation mode of the FRPSPDIS function. When output
signal STCNDZis selected, the characteristic for the FRPSPDIS (and also zone
measurement depending on settings) can be reduced by the load encroachment
characteristic (as shown in figure
Section 8
1MRK 506 369-UEN B
Impedance protection
314
Line distance protection REL670 2.2 IEC
Application manual