220kV Busbar
300/1
15 / 0,1
kV
4000/5
100 MVA
242/15,65 kV
Yd5
U
L1L2
, U
L2L3
G
P
Q
100MVA
15,65kV
IEC09000041-1-en.vsd
IED
IEC09000041-1-EN V1 EN-US
Figure 392:
Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure
, it is
necessary to do the following:
1. Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef
“Setting of the phase reference channel”
) using
PCM600 for analog input channels
2. Connect, in PCM600, measurement function to the generator CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
Section 18
1MRK 506 369-UEN B
Monitoring
774
Line distance protection REL670 2.2 IEC
Application manual