![ABB REL670 2.2 IEC Applications Manual Download Page 203](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789203.webp)
Reverse zone
SEMOD168247-222 v3
The reverse zone that is normally used in the communication schemes for functions
like fault current reversal logic, weak-in-feed logic or issuing carrier send in
blocking scheme must detect all faults in the reverse direction which is detected in
the opposite IED by the overreaching zone 2. The maximum reach for the
protection in the opposite IED can be achieved with the series capacitor in
operation.
The reactive reach can be set according to the following formula: X1 = 1.3 ·
(X1
2Rem
- 0.5 · (X1
L
- X
C
))
Settings of the resistive reaches are according to the minimum load impedance:
Optional higher distance protection zones
SEMOD168247-226 v2
When some additional distance protection zones (zone 4, for example) are used
they must be set according to the influence of the series capacitor.
8.1.3.6
Setting of zones for parallel line application
SEMOD168247-48 v2
Parallel line in service – Setting of zone1
SEMOD168247-50 v2
"Parallel line application with mutual coupling"
reach can be set to 85% of protected line.
Parallel line in service – setting of zone2
SEMOD168247-53 v2
Overreaching zones (in general, zones 2 and 3) must overreach the protected circuit
in all cases. The greatest reduction of a reach occurs in cases when both parallel
circuits are in service with a single phase-to-earth fault located at the end of a
protected line. The equivalent zero-sequence impedance circuit for this case is
equal to the one in figure
The components of the zero-sequence impedance for the overreaching zones must
be equal to at least:
R
0E
R
0
R
m0
+
=
EQUATION553 V1 EN-US
(Equation 76)
X
0E
X
0
X
m0
+
=
EQUATION554 V1 EN-US
(Equation 77)
Check the reduction of a reach for the overreaching zones due to the effect of the
zero sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1
0
m
f
Z
K
Z
Z
R
= -
×
+
+
EQUATION1426 V1 EN-US
(Equation 78)
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
197
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...