For the L1-L2 element, the equation in forward direction is according to.
1 2
1 2
1 2
0.8
1
0.2
1
arg
Re
L L
L L M
L L
U
U
ArgDir
ArgNeg
s
I
×
+
×
-
<
<
EQUATION726 V2 EN-US
(Equation 147)
where:
ArgDir
is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure
1
1
L
U
is positive sequence phase voltage in phase L1
1
1
L M
U
is positive sequence memorized phase voltage in phase L1
1
L
I
is phase current in phase L1
1 2
1
L L
U
is voltage difference between phase L1 and L2 (L2 lagging L1)
1 2
1
L L M
U
is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
1 2
L L
I
is current difference between phase L1 and L2 (L2 lagging L1)
The setting of
ArgDir
and
ArgNegRes
is by default set to 15 (= -15) and 115
degrees respectively (as shown in figure
). It should not be changed unless
system studies have shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the
output STDIRCND.
STDIR=
STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
233
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...