24.9.1
Application
SEMOD55213-5 v4
The Signal matrix for binary outputs function SMBO is used within the
Application Configuration tool in direct relation with the Signal Matrix tool.
SMBO represents the way binary outputs are sent from one IED configuration.
24.9.2
Setting guidelines
SEMOD55228-5 v2
There are no setting parameters for the Signal matrix for binary outputs SMBO
available to the user in Parameter Setting tool. However, the user must give a name
to SMBO instance and SMBO outputs, directly in the Application Configuration
tool. These names will define SMBO function in the Signal Matrix tool.
24.10
Signal matrix for mA inputs SMMI
SEMOD55233-1 v2
24.10.1
Application
SEMOD55237-5 v2
The Signal matrix for mA inputs function SMMI is used within the Application
Configuration tool in direct relation with the Signal Matrix tool. SMMI represents
the way milliamp (mA) inputs are brought in for one IED configuration.
24.10.2
Setting guidelines
SEMOD55247-5 v2
There are no setting parameters for the Signal matrix for mA inputs SMMI
available to the user in the Parameter Setting tool. However, the user must give a
name to SMMI instance and SMMI inputs, directly in the Application
Configuration tool.
24.11
Signal matrix for analog inputs SMAI
SEMOD55751-1 v2
24.11.1
Application
SEMOD55744-4 v10
Signal matrix for analog inputs (SMAI), also known as the preprocessor function
block, analyses the connected four analog signals (three phases and neutral) and
calculates all relevant information from them like the phasor magnitude, phase
angle, frequency, true RMS value, harmonics, sequence components and so on.
This information is then used by the respective functions connected to this SMAI
block in ACT (for example protection, measurement or monitoring functions).
1MRK 506 369-UEN B
Section 24
Basic IED functions
Line distance protection REL670 2.2 IEC
861
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...