will close at exactly the right instance if the networks run with a frequency
difference.
To avoid overlapping of the synchronizing function and the
synchrocheck function the setting
FreqDiffMin
must be set to a
higher value than used setting
FreqDiffM
, respective
FreqDiffA
used for synchrocheck.
FreqDiffMax
The setting
FreqDiffMax
is the maximum slip frequency at which synchronizing is
accepted. 1/
FreqDiffMax
shows the time for the vector to move 360 degrees, one
turn on the synchronoscope, and is called Beat time. A typical value for
FreqDiffMax
is 200-250 mHz, which gives beat times on 4-5 seconds. Higher
values should be avoided as the two networks normally are regulated to nominal
frequency independent of each other, so the frequency difference shall be small.
FreqRateChange
The maximum allowed rate of change for the frequency.
CloseAngleMax
The setting
CloseAngleMax
is the maximum closing angle between bus and line at
which synchronizing is accepted. To minimize the moment stress when
synchronizing near a power station, a narrower limit should be used. A typical
value is 15 degrees.
tBreaker
The
tBreaker
shall be set to match the closing time for the circuit breaker and
should also include the possible auxiliary relays in the closing circuit. It is
important to check that no slow logic components are used in the configuration of
the IED as there then can be big variations in closing time due to those
components. Typical setting is 80-150 ms depending on the breaker closing time.
tClosePulse
The setting for the duration of the breaker close pulse.
tMaxSynch
The setting
tMaxSynch
is set to reset the operation of the synchronizing function if
the operation does not take place within this time. The setting must allow for the
setting of
FreqDiffMin
, which will decide how long it will take maximum to reach
phase equality. At the setting of 10 mHz, the beat time is 100 seconds and the
setting would thus need to be at least
tMinSynch
plus 100 seconds. If the network
frequencies are expected to be outside the limits from the start, a margin needs to
be added. A typical setting is 600 seconds.
Section 15
1MRK 506 369-UEN B
Control
610
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...