![ABB REL670 2.2 IEC Applications Manual Download Page 792](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789792.webp)
Trip value rec
Fault locator
Event list
Event recorder
Indications
Disturbance
recorder
Disturbance Report
Binary signals
Analog signals
DRPRDRE
FL
IEC09000336-3-en.vsdx
AxRADR
BxRBDR
IEC09000336 V3 EN-US
Figure 394:
Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also
influences the sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quick
status information about the IED.
Green LED:
Steady light
In Service
Flashing light
Internal failure
Dark
No power supply
Yellow LED:
Steady light
Triggered on binary signal N with SetLEDx = Start (or Start and
Trip)
Flashing light
The IED is in test mode
Red LED:
Steady light
Triggered on binary signal N with SetLEDx = Trip (or Start and
Trip)
Flashing
The IED is in configuration mode
Section 18
1MRK 506 369-UEN B
Monitoring
786
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...