end by setting the corresponding LDCM to channel mode
Blocked
. If
OutOfService
is selected, the IED should have active communication to the remote end during the
whole maintenance process, that is, no restart or removal of the fiber can be done.
This setting does not apply to two-end communication.
Blocked
IED does not use data from the LDCM
OutOfService
IED informs the remote end that it is out of service
TerminalNo
is used to assign a unique address to each LDCM in all current
differential IEDs. Up to 256 LDCMs can be assigned a unique number. For
example, in a local IED with two LDCMs:
•
LDCM for slot 305: set
TerminalNo
to 1 and
RemoteTermNo
to 2
•
LDCM for slot 306: set
TerminalNo
to 3 and
RemoteTermNo
to 4
In multiterminal current differential applications,with 4 LDCMs in each IED, up to
20 unique addresses must be set.
A unique address is necessary to give high security against
incorrect addressing in the communication system. If the same
number is used for
TerminalNo
in some of the LDCMs, a loop-back
test in the communication system can give an incorrect trip.
RemoteTermNo
is used to assign a number to each related LDCM in the remote
IED. For each LDCM,
RemoteTermNo
is set to a different value than
TerminalNo
,
but equal to the
TerminalNo
of the remote end LDCM. In the remote IED,
TerminalNo
and
RemoteTermNo
are reversed as follows:
•
LDCM for slot 305: set
TerminalNo
to 2 and
RemoteTermNo
to 1
•
LDCM for slot 306: set
TerminalNo
to 4 and
RemoteTermNo
to 3
The redundant channel is always configured to the lower position,
for example:
•
Slot 305: main channel
•
Slot 306: redundant channel
The same is applicable for slot 312-313 and slot 322-323.
DiffSync
defines the method of time synchronization for the line differential
function:
Echo
or
GPS
.
Section 22
1MRK 506 369-UEN B
Remote communication
846
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...