3
U
0
UL
1
IEC07000190-2-en.vsd
IEC07000190 V2 EN-US
Figure 287:
Earth fault in Non-effectively earthed systems
10.3.3.5
Direct earthed system
GUID-EA622F55-7978-4D1C-9AF7-2BAB5628070A v8
In direct earthed systems, an earth fault on one phase is indicated by voltage
collapse in that phase. The other healthy phase will still have normal phase-to-earth
voltage. The residual sum will have the same value as the remaining phase-to-earth
voltage, which is shown in Figure
UL
1
IEC07000189-2-en.vsd
IEC07000189 V2 EN-US
Figure 288:
Earth fault in Direct earthed system
1MRK 506 369-UEN B
Section 10
Voltage protection
Line distance protection REL670 2.2 IEC
543
Application manual