Normally the voltage can be increased to higher values than the calculated
minimum
U>Trip
with a minor change of total operating values as long as this is
done by adjusting the resistor to a higher value. Check the sensitivity calculation
below for reference.
Table 16:
1 A channels: input with minimum operating down to 40 mA
Operating
voltage
U>Trip
Stabilizing
resistor R
ohms
Operating
current level
1 A
Stabilizing
resistor R
ohms
Operating
current level
1 A
20 V
500
0.040 A
--
--
40 V
1000
0.040 A
--
--
60 V
1500
0.040 A
600
0.100 A
80 V
2000
0.040 A
800
0.100 A
100 V
2500
0.040 A
1000
0.100 A
150 V
3750
0.040 A
1500
0.100 A
200 V
5000
0.040 A
2000
0.100 A
Table 17:
5 A channels: input with minimum operating down to 100 mA
Operating
voltage
U>Trip
Stabilizing
resistor R1
ohms
Operating
current level
5 A
Stabilizing
resistor R1
ohms
Operating
current level
5 A
Stabilizing
resistor R1
ohms
Operating
current level
5 A
20 V
200
0.100 A
100
0.200 A
--
--
40 V
400
0.100 A
200
0.200 A
100
0.400
60 V
600
0.100 A
300
0.200 A
150
0.400 A
80 V
800
0.100 A
400
0.200 A
200
0.400 A
100 V
1000
0.100 A
500
0.200 A
250
0.400 A
150 V
1500
0.100 A
750
0.200 A
375
0.400 A
200 V
2000
0.100 A
1000
0.200 A
500
0.400 A
The current transformer saturation voltage must be at least 2 ˣ
U>Trip
to have
sufficient operating margin. This must be checked after calculation of
U>Trip
.
When the R value has been selected and the
U>Trip
value has been set, the
sensitivity of the scheme
IP
can be calculated. The IED sensitivity is decided by
the total current in the circuit according to equation
.
(
)
IP
n IR Ires
lmag
= ×
+
+
å
EQUATION1747 V1 EN-US
(Equation 14)
where:
n
is the CT ratio
IP
primary current at IED pickup,
Table continues on next page
1MRK 506 369-UEN B
Section 7
Differential protection
Line distance protection REL670 2.2 IEC
133
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...