PSPPPAM function shall detect out of step conditions and trip the generator as fast
as possible if the locus of the pole slip is inside the generator. If the centre of pole
slip is outside the generator, situated out in the power grid, the first action should
be to split the network into two parts, after line protection action. If this fails there
should be operation of the generator pole slip protection, to prevent further
damages to the generator block.
8.16.3
Setting guidelines
SEMOD167596-1 v1
SEMOD167582-4 v4
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
Operation
: With the parameter
Operation
the function can be set
On
or
Off
.
MeasureMode
: The voltage and current used for the impedance measurement is set
by the parameter
MeasureMode
. The setting possibilities are:
PosSeq
,
L1-L2
,
L2-
L3
, or
L3-L1
. If all phase voltages and phase currents are fed to the IED the
PosSeq
alternative is recommended (default).
Further settings can be illustrated in figure
.
Section 8
1MRK 506 369-UEN B
Impedance protection
426
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...