Table 57:
General settings parameters for the Measurement function
Setting
Short description
Selected
value
Comment
Operation
Operation
Off/On
On
Function must be
On
PowAmpFact
Amplitude factor to scale power
calculations
1.000
Typically no scaling is required
PowAngComp
Angle compensation for phase
shift between measured I & U
180.0
Typically no angle compensation
is required. However here the
required direction of P & Q
measurement is towards busbar
(Not per IED internal default
direction). Therefore angle
compensation have to be used in
order to get measurements in
aliment with the required
direction.
Mode
Selection of measured current
and voltage
L1L2
Only UL1L2 phase-to-phase
voltage is available
k
Low pass filter coefficient for
power measurement, U and I
0.00
Typically no additional filtering is
required
UGenZeroDb
Zero point clamping in % of
Ubase
25
Set minimum voltage level to
25%
IGenZeroDb
Zero point clamping in % of
Ibase
3
Set minimum current level to 3%
UBase (set in
Global base)
Base setting for voltage level in
kV
35.00
Set LV side rated phase-to-
phase voltage
IBase (set in
Global base)
Base setting for current level in
A
495
Set transformer LV winding rated
current
SBase (set in
Global base)
Base setting for power in MVA
31.5
Set based on rated power
Measurement function application for a generator
SEMOD54481-110 v8
Single line diagram for this application is given in figure
1MRK 506 369-UEN B
Section 18
Monitoring
Line distance protection REL670 2.2 IEC
773
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...