XHiLim
: High limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for Voltage
measurement and
IBase
for current measurement).
XLowLim
: Low limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for Voltage
measurement and
IBase
for current measurement).
XLowLowLim
: Low-low limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for
Voltage measurement and
IBase
for current measurement).
XLimHyst
: Hysteresis value in % of range and is common for all limits.
All phase angles are presented in relation to defined reference channel. The
parameter
PhaseAngleRef
defines the reference, see Section
.
Calibration curves
It is possible to calibrate the functions (CVMMXN, CMMXU, VMMXU and
VNMMXU) to get class 0.5 presentations of currents, voltages and powers. This is
accomplished by amplitude and angle compensation at 5, 30 and 100% of rated
current and voltage. The compensation curve will have the characteristic for
amplitude and angle compensation of currents as shown in figure
(example).
The first phase will be used as reference channel and compared with the curve for
calculation of factors. The factors will then be used for all related channels.
IEC05000652 V2 EN-US
Figure 389:
Calibration curves
Section 18
1MRK 506 369-UEN B
Monitoring
768
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...