Station HMI
GW
cc
Station bus
breakers disconnectors earthing switches
IEC08000227.vsd
Apparatus
Control
IED
I/O
Local
HMI
Apparatus
Control
IED
I/O
Apparatus
Control
IED
I/O
Local
HMI
Local
HMI
IEC08000227 V1 EN-US
Figure 312:
Overview of the apparatus control functions
Features in the apparatus control function:
•
Operation of primary apparatuses
•
Select-Execute principle to give high security
•
Selection and reservation function to prevent simultaneous operation
•
Selection and supervision of operator place
•
Command supervision
•
Block/deblock of operation
•
Block/deblock of updating of position indications
•
Substitution of position indications
•
Overriding of interlocking functions
•
Overriding of synchrocheck
•
Pole discordance supervision
•
Operation counter
•
Suppression of mid position
The apparatus control function is realized by means of a number of function blocks
designated:
•
Switch controller SCSWI
•
Circuit breaker SXCBR
•
Circuit switch SXSWI
•
Bay control QCBAY
•
Bay reserve QCRSV
Section 15
1MRK 506 369-UEN B
Control
640
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...